IEC/TS 60479-1 Ed. 4.0 Edition 07/2005
Effects of current on human beings and livestock - Part 1: General aspects
  •   
  •  
  • 304.6 / copy
  •  
 

Abstract

IEC 60479-1:2005 For a given current path through the human body, the danger to persons depends mainly on the magnitude and duration of the current flow. However, the time/current zones specified in this publication are, in many cases, not directly applicable in practice for designing measures of protection against electrical shock. The necessary criterion is the admissible limit of touch voltage (i.e. the product of the current through the body called touch current and the body impedance) as a function of time. The relationship between current and voltage is not linear because the impedance of the human body varies with the touch voltage, and data on this relationship is therefore required. The different parts of the humanbody (such as the skin, blood, muscles, other tissues and joints) present to the electric current a certain impedance composed of resistive and capacitive components. The values of body impedance depend on a number of factors and, in particular, on current path, on touch voltage, duration of current flow, frequency, degree of moisture of the skin, surface area of contact, pressure exerted and temperature. The impedance values indicated in this technical specification result from a close examination of the experimental results available from measurements carried out principally on corpses and on some living persons. It has the status of a horizontal standard in accordance with IEC Guide 104. The contents of the corrigenda of October 2006 and June 2013 have been included in this copy.

Status

Standard - Active

Origin

Technical Committee :
64 : Electrical installations and protection against electric shock

Implementation

start of the vote on the project      date of ratification (dor)   
end of the vote on the project      date of anouncement (doa)   
start of the vote on the final project      date of publication (dop)   
end of the vote on the final project      date of withdrawal (dow)   


Publication Official Journal
of the Grand-Duchy of Luxembourg
Reference

Relations

Evolutions
IEC 60951-3 Ed.3.0 RLV
IEC 60479-1 Ed.1.0

International Classification for Standards (ICS codes) :

13.200 : Accident and disaster control
29.020 : Electrical engineering in general